Permit NumberFIR07-00908
StatusFinaled
Name QUALITY ELECTRIC INC
Site Address 300 E JEFFERSON ST
Project NameST LUKES MOB - 2ND FLR
Customer Number 
ePlanReview 
Description
This fire alarm permit is to relocate several existing smoke detectors, notification appliances, and provide several new notification appliances and a new NAC booster panel on the 1st floor of the St Lukes JMOP building. BLD07-01230s to remodel an existing 980 sq. ft. medical office suite to create (5) new exam rooms, a Nurse Station, access hall and Check/In - Check/Out reception counter. Work includes selective interior demolition; new accessible reception counter/new opening though existing wall into existing shared waiting area; new cabinetry, accessible doors and hardware; modify electrical, plumbing, mechanical, fire sprinkler and alarm systems to meet tenant needs and provide compliance with current adopted codes and ordinances. Drs NOTE: This building is fully sprinklered to allow wood frame third floor and as substitute for rated corridors under 1991UBC.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/7/200712/10/200712/10/2007APASS
DetailsForrest France
Verified corrections, fire alarm testing passed, noted map at the panel to be updated with correct SD addresses.
INSP-Final Inspection12/6/200712/7/200712/10/2007AFAIL
DetailsForrest France
SD address changes do not match approved plan set, need to change cd at the reception area notification device, also need to test new NAC.