INSP-Final Inspection | 5/13/2008 | 5/13/2008 | 5/13/2008 | P | PASS |
Forrest France
|
|
|
Defficient items retested, correction notice finished, fire alarm permit finaled.
|
INSP-Final Inspection | 5/7/2008 | 5/8/2008 | 5/9/2008 | P | FAIL |
Forrest France
|
|
|
Three wall post tampers at the main riser manifold need to be wired in the normally open condition, flow switch at riser #1 is out of adjustment, provide a map at the FACP per review note #10, descriptor at the west floor shop WP is not accurate. Remainder of fire alarm work passed testing.
|
FIR-Aging Inspection | 2/7/2008 | 2/8/2008 | 2/12/2008 | A | DEFR |
Forrest France
|
|
|
Need site inspection request from contractor when work is completed.
|