Permit Information
Permit NumberFIR07-00934
StatusFinaled
Name GENERAL FIRE INC
Site Address 11311 W CHINDEN BLVD
Project NameHewlett-Packard
Customer Number 
ePlanReview 
Description
Cooking Hood
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/20/20083/21/20083/21/2008APASS
DetailsTroy Cobbley
Hood inspections complete.Repairs corrected per last inspection.KR
INSP-Final Inspection2/12/20082/12/20082/12/2008PFAIL
DetailsTroy Cobbley
Per ANSUL the nozzles in the ducting need approval from them prior to acceptance of the hood. The nozzles in the duct are installed at the top where as the installation guide and past installs the nozzles are installed at the bottom of the duct. Ken took pictures of the installation and will email them to his contact at ANSUL corporate. This was done to facilitate the approval of this permit for the fire suppression contractor and provide clarification to the inspectors.
INSP-Final Inspection1/30/20081/30/20081/30/2008PFAIL
DetailsTroy Cobbley
Nozzles had not been installed in the plenum as required by Ansul. Inspection was stopped until this work is completed on both hoods.