Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR07-00993
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 3138 S BOWN WAY
Project NameSPR-O'neill Enterprises
Customer Number 
ePlanReview 
Description
Installing 12 new SSP's to accomodate new tenant ceiling an wall modifications. This fire sprinkler work is associated with BLD07-02132.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/22/20081/22/20081/22/2008PPASS
DetailsForrest France
Fire sprinkler permit okay for final, field ceiling tile to be installed today per contractor-verified at structural final.
INSP-Sprinkler Rough-in1/17/20081/17/20081/17/2008PPART
DetailsForrest France
Overhead fire sprinkler work is approved for cover at the drop ceiling areas.
INSP-Sprinkler Rough-in1/11/20081/11/20081/11/2008PFAIL
DetailsTroy Cobbley
Upright protection has been added only at the locations where the combustibles are. The combustible do not meet the definition of nfpa 13 8.14.1.5 (1). Provide upright protection throughout the attic space and resubmit plans showing the additional heads.
INSP-Sprinkler Rough-in1/7/20081/8/20081/8/2008PFAIL
DetailsForrest France
Missing coverage for combustible construction at the spaces above the drop ceiling.