Permit Information
Permit NumberFIR07-01013
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 6300 N ROE ST
Project NameThe cottages of boise #1
Customer Number 
ePlanReview 
Description
The Permitted Work Scope: Over head: Beginning from an existing 6” underground supply in the riser room, install a 4” manifold and a 4” dry pipe riser to serve through out the interior and attic space.
Under separate permit: FIR07-00887; Under ground: Beginning from an NRS valve located off of Roe Street, install a post indicating control valve and run 60 lf. of 6” C-900 out and stub up into the riser room of a new 8’683-ft/2 VB type constructed 1 story bldg. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2003,
The fire sprinkler system work shall comply with IFC 2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to permit BLD05-01603 and UG permit # FIR07-00887.
01/21/08 Comments & Conditions:
A forward flow assembly is required. To be field verified.
2. The unsprinklered roof dormers / overbuilds appear to be 5’-0” + at the peak. Note: At the time of rough in or final inspection, please provide a view port at each dormer so that the dormer insulation level may be confirmed by a Fire/Life Safety inspector.
01/21/08 Noted. The Building Department has been notified.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled  7/2/2008 DONE
Fire Life safety passed by Troy Cobbley on 6-5-08 BAS
INSP-Final Inspection5/30/20086/2/20086/2/2008ACANC
DetailsTroy Cobbley
Jeremiah, please call 30 minutes prior; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
INSP-Sprinkler Rough-in/Hydro5/13/20085/14/20085/14/2008APASS
DetailsTroy Cobbley
24 hr air test passed
INSP-Sprinkler Rough-in/Hydro5/12/20085/13/20085/13/2008PPASS
DetailsTroy Cobbley
24 hr air test started at 10:30 with 43psi on the guage.
INSP-Sprinkler Rough-in/Hydro2/19/20082/20/20082/20/2008PPASS
DetailsTroy Cobbley
The wet system and dry system hydro tests passed.
INSP-Sprinkler Rough-in/Hydro2/15/20082/15/20082/15/2008PFAIL
DetailsTroy Cobbley
The inspection was for above ground hydo tests. The dry system had lost pressure prior to me arriving. I also that the FDC was not being hydro as required. The wet system did have over 200 lbs. The fitter and I decided that all of the testing for buildings 1 and 2 as well as the rough in for buidling 2 will happen on wednesday.
INSP-Sprinkler Rough-in/Hydro2/12/20082/12/20082/12/2008PPASS
DetailsTroy Cobbley
The sprinkler piping is ok to cover. Per a verbal agreement with the general contractor the overbuild areas wont be covered until I can verify that they are full of insulation as per the approved plans.
INSP-Sprinkler Rough-in2/5/20082/7/20082/7/2008APART
DetailsTroy Cobbley
The overbuilds need to be filled with insulation as per the approved drawings. A hanger/block assembly on the wet system needs replaced. Tenting needs repaired. The inspectors test for the dry system needs to be located at the end of the most remote branchline as stated in NFPA 13 8.16.4