Permit Information
Permit NumberFIR07-01026
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 101 S CAPITOL BLVD Unit: 1200
Project Name 
Customer Number 
ePlanReview 
Description
Work Scope: Over Head Only
Add and relocate new QR concealed heads to accommodate a new wall and ceiling layout on the 12th floor of this 20 story high rise bldg. Mechanical tee’s will be added were necessary to supply a new head location. The approved scope of work is limited to the area noted on these plans. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD07-02948. When tenant work affects fire sprinkler protection outside the permitted work area due to the installation of tenant-demising or new partition walls, the affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The “Riser” and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/13/20082/13/20082/13/2008PPASS
DetailsForrest France
Fire sprinkler permit finaled, agreed to apply NFPA 13 2007 sec. 3.3.15 to define "small room" regarding spacing issues at the offices in question.
INSP-Final Inspection2/5/20082/6/20082/6/2008PFAIL
DetailsForrest France
Offices at some locations are overspaced due to room construction not meeting the criteria for the "small room" rule.
INSP-Sprinkler Rough-in1/9/20081/11/20081/11/2008APART
DetailsForrest France
OH rough-in is approved for cover at the drop ceiling areas- see approved plans for annotations.