Permit NumberFIR08-00037
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 1050 W RIVER ST
Project Name 
Customer Number 
ePlanReview 
Description
overhead Work Scope: Over Head Only
Modify the existing wet pipe sprinkler system in the Main, East & West offices on the 1st floor of this 2 story bldg. to accommodate a new ceiling layout and remodel. The scope includes adding and relocating sprinkler heads. The scope also includes tieing into the existing 2” supply in the East office to supply new branchlines. (See Sheet FP2) The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to permit BLD07-02914. When tenant work affects fire sprinkler protection outside the permitted work area due to the installation of tenant-demising or new partition walls, the affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The “Riser” and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/27/20082/29/20082/29/2008PPASS
DetailsForrest France
Final fire sprinkler inspection passed, permit finaled.
INSP-Sprinkler Rough-in/Hydro2/26/20082/27/20082/27/2008APART
DetailsForrest France
OH hydrostatic test for the east office area new branch lines and main passed inspection.
INSP-Sprinkler Rough-in2/18/20082/20/20082/20/2008PPART
DetailsForrest France
See areas on approved plans okayed for cover, noted missing unistrut clamps at two locations on the 1 1/2 main, tie-in and EQ brace at the 2" main and 1 1/2 mains are not yet completed, need one upright installed at open office area south side, some noted items from previous inspection are finished, need to complete a hydrostatic test at the east office area new main and branch lines.
INSP-Sprinkler Rough-in2/13/20082/14/20082/14/2008APART
DetailsForrest France
See annotations on stamped plans for areas okayed for ceiling cover, noted seven heads at various locations that will need changed to QR, also noted obstructions to discharge at the server room, one painted ssu needs to be replaced.
INSP-Sprinkler Rough-in2/5/20082/6/20082/6/2008APART
DetailsForrest France
See approved plans for areas circled and initialed as okay for cover at the hard lid ceilings, be aware of possible light fixture obstructions due to surface mounted lights not installed at this time.
INSP-Sprinkler Rough-in2/4/20082/5/20082/5/2008PCANC
DetailsForrest France
OH Cover Inspection
Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley