Permit Information
Permit NumberFIR08-00066
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 190 E FRONT ST
Project NameCOURTHOUSE
Customer Number 
ePlanReview 
Description
overhead Work Scope:
(ADA COUNTY - ASSESSORS OFFICE) To construct a core and shell and office build out for a 14,380 sq.ft. tenant space which includes minor interior demolition, replacing storefront doors with glazing and a new exterior entry vestibule and window decorative sunscreens per approved plans and DRH07-00359. Work includes construction of non-combustible fire-resistive wall partitions to create private offices, three distinct open office customer service and support areas, a break area, vault, file and conference areas; four fully accessible restrooms, drinking fountains and customer service counters; new suspended ceiling grid system and electrical, mechanical, plumbing, sprinkler and alarm system upgrades to meet tenant needs and provide code compliance.
The Fire Sprinkler scope consists of adding and relocating down heads to accommodate the new wall and ceiling layout. The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD07-03027.
When tenant work affects fire sprinkler protection outside the permitted work area due to the installation of tenant-demising or new partition walls, the affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The “Riser” and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/20/20087/21/20087/21/2008APASS
DetailsForrest France
Correction notice items are complete, final fire sprinkler inspection passed, permit finaled.
INSP-Final Inspection7/17/20087/18/20087/18/2008APART
DetailsForrest France
Need to provide matched temperature heads at the east mechanical room. Remainder of fire sprinkler work is acceptable and okay for final once correction is made.
INSP-Sprinkler Rough-in6/23/20086/24/20086/24/2008APART
DetailsForrest France
Overhead rough-in is okay for cover at the drop ceilings, verified corrections, one head at the OTS mech. room east side remains to be relocated.
INSP-Sprinkler Rough-in6/18/20086/19/20086/19/2008PFAIL
DetailsForrest France
Armover hangers at several locations do not meet requirements of NFPA 13 2007 9.2.3.5.2.1, two heads adjacent to a continuous ceiling obstruction do not meet table 8.6.5.1.2, missing one head per drawings not installed, noted overspaced heads at four locations including a small room and open office areas, heads at an east side OTS room need relocated to avoid obstructions and meet head listing, overhead install is not approved for cover at this time.
INSP-Sprinkler Rough-in5/1/20085/2/20085/2/2008APART
DetailsForrest France
See approved plans for areas previously marked as okay for cover-no new hard lids to inspect at this time, new south entrance vestibule is not yet piped, be aware of possible obstructions/spacing issues at the front soffits depending on drop ceiling heights and head locations.
INSP-Sprinkler Rough-in4/21/20084/21/20084/22/2008PPASS
DetailsTroy Cobbley
See the city approved plans for new areas that are marked ok to cover.
INSP-Sprinkler Rough-in4/16/20084/16/20084/16/2008PPART
DetailsForrest France
Okayed overhead rough-in at the hard lid ceilings as red lined with todays date on stamped plans.