Permit Information
Permit NumberFIR08-00076
StatusFinaled
Name AIC SOLUTIONS INC
Site Address 6411 W FAIRFIELD AVE
Project NameMcKinley Elementary School
Customer Number 
ePlanReview 
Description
Installation of a new fire alarm system in a new elementary school. BLD07-00143.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/30/20085/30/20085/30/2008PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection5/27/20085/28/20085/28/2008AFAIL
DetailsTroy Cobbley
Provide factory verification that the duct smoke detector at address 45 can be located as installed. All other items are complete.
INSP-Final Inspection5/21/20085/22/20085/22/2008AFAIL
DetailsTroy Cobbley
Provide modifications to the attic area a/v's as discussed to meet code requirements. Need to test the duct smoke detectors and in-duct detectors in heat mode to verify shutdown. Many of the main level a/v's are not using temporal but are sounding with two pulses the same time as other are doing the temporal. The a/v in room 202 is overspaced. As-builts will be needed prior to sign off of this permit.
INSP-Final Inspection5/20/20085/21/20085/21/2008AFAIL
DetailsTroy Cobbley
The sprinkler interconnections were tested today. The tamper switches had to be adjusted so they would activate correctly. The riser waterflow switches and tamper switches need to be relabeled so that they matched the sprinkler contractors designations as sprinkler riser 1 and sprinkler riser 2. The horn in the electrical room was not sounding in a temporal pattern. After all of that was fixed I spent the remaining time testing all of the manual pull stations.