INSP-Final Inspection | 5/20/2008 | 5/21/2008 | 5/21/2008 | P | PASS |
Forrest France
|
|
|
Corrections are complete, remainder of fire alarm testing passed inspection, map at the panel to be provided as discussed and verified at tomorrow's site visit, permit finaled.
|
INSP-Final Inspection | 5/19/2008 | 5/20/2008 | 5/20/2008 | P | FAIL |
Forrest France
|
|
|
Need to provide an updated map at the panel, SD at one DH is located too close to an HVAC grill, sample and vent tubes for all duct detectors must be installed and oriented per manufacturers instructions and data sheets.
|
FIR-Aging Inspection | 5/13/2008 | 5/13/2008 | 5/13/2008 | | DONE |
Forrest France
|
|
|
Construction underway, work in progress.
|