Permit Information
Permit NumberFIR08-00091
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 2537 W STATE ST Unit: 102
Project NameST MARY'S CROSSING
Customer Number 
ePlanReview 
Description
To install one duct detector to an existing building fire alarm system.BLD07-02852
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/3/20083/3/20083/3/2008PPASS
DetailsForrest France
Duct detectors at two locations have been removed due to HVAC capacities below limits required for device installation.
INSP-Alarm Testing2/28/20082/29/20082/29/2008PFAIL
DetailsForrest France
HVAC fans need to shut down upon activation of the duct smoke detection device.