INSP-Final Inspection | 8/4/2008 | 8/4/2008 | 8/4/2008 | A | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Final Inspection | 6/23/2008 | 6/23/2008 | 6/26/2008 | P | NH |
Forrest France
|
|
|
Larren Phone #: ###-####
|
INSP-Final Inspection | 6/17/2008 | 6/17/2008 | 6/23/2008 | P | DEFR |
Forrest France
|
|
|
Larren; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
|
INSP-Final Inspection | 6/16/2008 | 6/16/2008 | 6/16/2008 | A | PART |
Forrest France
|
|
|
Final pending repair of the non-functional outside waterflow bell.
|
INSP-Final Inspection | 5/28/2008 | 5/28/2008 | 5/28/2008 | P | FAIL |
Troy Cobbley
|
|
|
Photo room removed per Forrest notes. Waterflow bell out side in front of building did not function. Will call in for re-test. KR
|
INSP-Final Inspection | 3/26/2008 | 3/27/2008 | 3/27/2008 | A | PART |
Forrest France
|
|
|
Scope of work is not complete due to pending demolition of the photo room, conference room pendent heads are satisfactory. Also noted non-functional outside waterflow bell to be repaired and verified at next site visit for permit final.
|