Permit Information
Permit NumberFIR08-00158
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 700 N ANCESTOR PL
Project NameSPR-UNG SuperValu Data Center
Customer Number 
ePlanReview 
Description
To install 35 feet of 6 inch C-900 fire sprinkler supply piping into new building addition. This work is associated with BLD07-03132. *Important* 1. This approval is for the construction and installation of underground sprinkler supply piping, fittings and associated valves only.
2. This underground fire sprinkler plan has not been reviewed or approved with regard to the size of the main or future sprinkler system hydraulic demand. A copy of this approved underground plan, including notes and redline items, shall be included with the sprinkler permit plans and accurately reflected in the hydraulic calculations.
3. Final approval of the underground is contingent upon satisfactory hydraulic calculations of the sprinkler system.

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/12/20092/13/20092/13/2009PPASS
DetailsTroy Cobbley
permit finaled.
INSP-Supply line flush12/4/200812/5/200812/5/2008APASS
DetailsTroy Cobbley
Underground flush passed
INSP-Sprinkler Rough-in/Hydro12/1/200812/2/200812/2/2008APASS
DetailsTroy Cobbley
The underground hydro test passed.
INSP-Sprinkler Rough-in/Hydro11/26/200811/28/200811/28/2008ACANC
DetailsTroy Cobbley
BRIAN Phone #: ###-####
INSP-Sprinkler Rough-in11/21/200811/21/200811/21/2008PPART
DetailsForrest France
UG Cover okay per activity notes completed 6/27.
INSP-Sprinkler Rough-in6/26/20086/27/20086/27/2008APART
DetailsForrest France
Ok to cover 9' out from building. See city approved plans for details. KR
FIR-Aging Inspection6/3/20086/3/20086/4/2008 NR
DetailsTroy Cobbley
work in progress