Permit Information
Permit NumberFIR08-00164
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 509 W MCGREGOR CT
Project Name 
Customer Number 
ePlanReview 
Description
Work Scope: UG & OH: Federal Way Building #5 (Shell Only) - To construct a new 24,250 square foot, one story, concrete tilt-up office/warehouse and related site improvements. This is a shell permit only and no occupancy is allowed under this permit. Separate tenant improvement permits will be required to finish this building for occupancy. all construction per the approved plans and attached comment list.
UG Scope: Beginning from an existing 12” water line and an 8” NRS road box off of McGregor Drive, run 298’ LF of 8” C-900 pipe out and rise up into a new 24,250-ft/2 building with ductile iron. The UG installation shall conform to the applicable NFPA standards.
OH Scope: Beginning from an existing supply and an 8” flange located at the mid bldg. East side, install a 6” wet riser and wet pipe system to serve through out the entire bldg. The system is designed to Ordinary Group II for shell protection of the spec warehouse space designed to protect Class I – IV commodity up to 20’ in a palletized solid pile, bin box or shelf storage arrangement. The designer has included a 300 gpm allowance for a future rack system. Any future rack system shall be submitted separately from this permit. According to the general notes submitted, there will be no storage with in the warehouse until a tenant moves in.
The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD07-02855.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/12/20089/12/20089/12/2008PPASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection9/9/20089/10/20089/10/2008APART
DetailsForrest France
Items on correction notice have been verified for completion, permit final pending tamper and alarm device testing.
INSP-Final Inspection9/9/20089/9/20089/10/2008PFAIL
DetailsForrest France
Noted several spacing issues at the SW branch line adjacent to the overhead doors, missing PRV at the riser, trapeeze hanger at the last piece of 6" main is overspaced, FDC piping is missing hanger support and bracing at the vertical run, noted added head at the electrical room, provide riser tags, signage, DCVA certification, and complete forward flow testing in conjunction with riser supervision. Site inspection completed 9/9.
INSP-Final Inspection9/8/20089/8/20089/9/2008PNR
DetailsForrest France
Need approved plans on site.
INSP-Sprinkler Rough-in/Hydro9/4/20089/4/20089/4/2008APART
DetailsForrest France
Repairs completed, UG fire supply line hydrostatic testing passed. Noted missing sprinkler piping and head coverage at the electrical room adjacent to the riser, also noted FDC is over max. 4' above grade due to finish slope-see fire code review notes item #51 for FDC requirements. Overhead install not inspected to date.
INSP-Sprinkler Rough-in/Hydro8/14/20088/14/20088/14/2008PPASS
DetailsTroy Cobbley
Above ground hydro test passed.
INSP-Sprinkler Rough-in/Hydro7/29/20087/30/20087/30/2008APART
DetailsForrest France
UG fire supply line flush completed acceptable.
INSP-Sprinkler Rough-in6/3/20086/3/20086/3/2008PPART
DetailsForrest France
UG fire suply line installation appears satisfactory however the city stamped drawings and documents were not on site at the time of inspection per condition of the permit, will need to verify plans match install prior to final approval.