INSP-Final Inspection | 6/9/2008 | 6/10/2008 | 6/10/2008 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 6/6/2008 | 6/9/2008 | 6/9/2008 | A | FAIL |
Troy Cobbley
|
|
|
The secondary phone line could not be verified due to equipment failure. The strobes candella's as installed do not match the approved plans and are overspaced as installed. No testing performed. The sound levels were verified at 109db.
|
INSP-Sprinkler Rough-in/Hydro | 6/6/2008 | 6/9/2008 | 6/6/2008 | A | CANC |
Troy Cobbley
|
|
|
Troy, I left you a message about cancelling this inspection on Friday, and rescheduling it for today. Please call with an approximate time. Thank you. ###-#### Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
|
INSP-Final Inspection | 6/6/2008 | 6/6/2008 | 6/6/2008 | P | CANC |
Troy Cobbley
|
|
|
Troy, please call as soon as you know an approximate time. Thank You. ###-#### Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
|