INSP-Final Inspection | 9/30/2008 | 10/3/2008 | 10/3/2008 | A | PASS |
Troy Cobbley
|
|
|
All corrections made per Troys last inspection. KR
|
INSP-Final Inspection | 9/23/2008 | 9/26/2008 | 9/26/2008 | P | CANC |
Troy Cobbley
|
|
|
Could not do the inspection due to time constraints.
|
INSP-Final Inspection | 9/9/2008 | 9/17/2008 | 9/17/2008 | A | FAIL |
Troy Cobbley
|
|
|
The technician and I were not able to test the duct smoke detectors today due to not being able to put the detectors into heat mode for testing. Zone 7 indeterminant signal has not been checked either. The abandoned duct smoke detectors need to be removed as per IFC 901.4.4 and the wiring needs to be removed per NFPA 70 (NEC) 760.3 (a). The audio/visuals did test ok.
|
INSP-Final Inspection | 6/16/2008 | 6/17/2008 | 6/17/2008 | A | FAIL |
Troy Cobbley
|
|
|
The phone lines, flow switch and tamper switches tested ok. But a undefined signal came in for zone 7 which Brian is going to investigate it. We did not test the duct smoke detectors because the sample tubes extend out the back side of the duct work by up to 3' with the sample holes taped off with electrical tape. The first strobe that I looked at was overspaced off of the northwest wall. New walls are being built that are not shown on the plans and are effecting strobe placement. Due to the deficiencies listed above this test was a bust.
|