Permit Information
Permit NumberFIR08-00254
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 11760 W EXECUTIVE DR Unit: 140
Project NameRacking Permit
Customer Number 
ePlanReview 
Description
Bldg. Scope:
(SBI CONTRACTING RACKING - EXECUTIVE CENTER - STE 140) To install 198 lineal ft. of 6'-4" to 9'-10" high steel storage pallet racking in a 10,500 sq.ft. existing warehouse area per approved plans and Engineering. The design, testing and utilization of industrial steel storage racks shall be in accordance with the RMI Specification for the Design, Testing and Utilization of Industrial Steel Storage Racks. A Letter of Completion is to be issued when done. This building was originally constructed in Ada County and later annexed into Boise City. Existing envelope is not being affected by this permit. NOTE: This building is fully fire sprinklered for area increase. (SRZ)
Work Scope: OH
These plans were submitted for a complete evaluation of the existing system to confirm the existing design would support proposed rack storage of Class I – III to 16’-6” through out the warehouse. The existing system is designed to Ordinary Group II / Spec Warehouse @ .30/2600-ft/2. Two heads will be added for column protection as required.
The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD08-00653.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/14/20085/14/20085/14/2008PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro5/13/20085/14/20085/14/2008APASS
DetailsTroy Cobbley
rough-in passed