Permit Information
Permit NumberFIR08-00446
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 851 W FRONT ST Unit: 1201
Project NameTHE ASPEN - UNIT 1201
Customer Number 
ePlanReview 
Description
FIR OH Work Scope: Providing fire sprinkler coverage through out the unit. The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD08-01146.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/5/20101/5/20101/6/2010PPASS
DetailsForrest France
Fire sprinkler permit final approved.
INSP-Final Inspection12/28/200912/29/200912/29/2009AFAIL
DetailsForrest France
Heads at new 401 canopies have been installed via a series of 1/2" brass nipple extenders. See NFPA 13 2007 8.15.19.1.
INSP-Final Inspection12/23/200912/23/200912/23/2009PFAIL
DetailsTim Frost
Inspection failed due to 3 sprinklers that were blocked by lighting fixture. One of the sprinkler was also bent or installed crooked.
INSP-Sprinkler Rough-in/Hydro12/3/200912/3/200912/3/2009PNR
DetailsForrest France
INSP-Final Inspection9/1/20099/2/20099/4/2009ANR
DetailsForrest France
Project is not in condition for final at this time due to incompleted construction finishes, noted one SW head too far below the ceiling, and a missing head at a mechanical closet.
INSP-Final Inspection8/25/20098/26/20098/26/2009AFAIL
DetailsTroy Cobbley
One pendant in the master bath is overspaced from west wall, need ceiling and pendant installed in furnance room and the permanent lighting needs installed.
INSP-Sprinkler Rough-in/Hydro6/22/20096/23/20096/23/2009APART
DetailsForrest France
Overhead rough-in okayed for cover, one upright head removed while on site, be aware of possible light fixture obstructions due to junction box locations and pendent heads.
FIR-Aging Inspection10/21/200810/21/200810/21/2008 DONE
DetailsForrest France
Work in progress, construction underway.