INSP-Final Inspection | 9/9/2009 | 9/10/2009 | 9/10/2009 | A | PASS |
Forrest France
|
|
|
Correction notice items are completed, fire sprinkler permit finaled.
|
INSP-Final Inspection | 9/1/2009 | 9/2/2009 | 9/4/2009 | A | FAIL |
Forrest France
|
|
|
Missing coverage at a mechanical room, two pendent heads need changed to intermediate temp. due to proximity to heat sources per NFPA table 7.5.5.3.
|
INSP-Sprinkler Rough-in/Hydro | 6/22/2009 | 6/23/2009 | 6/23/2009 | A | FAIL |
Forrest France
|
|
|
Coverage is obstructed at one room, two pendent heads exceed min. spacing, one upright head needs removed.
|
FIR-Aging Inspection | 10/24/2008 | 10/24/2008 | 10/27/2008 | | DONE |
Forrest France
|
|
|
Work in progress, construction underway.
|