Permit Information
Permit NumberFIR08-00523
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 401 W FRONT ST
Project NameBELLA PLAZA OFFICE BLDG
Customer Number 
ePlanReview 
Description
This fire alarm permit is to add notification and initiating devices to an existing system to accommodate the tenant improvement of part of the 4th floor and all the 5th and 6th floors. Duct detectors are being added for three new roof top HVAC units. This permit scope also includes monitoring a new VESDA and preaction system.

Associated building permit: BLD08-01294 (MICROSOFT)**(Suites 401 / 500 / 600 Located on the 4th, 5th & 6th Floors)** (PARTIAL PERMIT ISSUED 6/13/08: SEE CONDITIONS STATEMENT) To remodel half of the 4th floor, 5th floor and 6th floor for a new tenant. The fourth floor will have an area of 7007 sq ft / the fifth floor area is 13,721 sq ft / and the sixth floor area is 13,721 sq ft. The total occupied tenant space will be 34,449 sq ft. Work to include, structural upgrades to the sixth floor to support the load of new servers, upgrades to the roof structure to support new HVAC roof top systems, construction of new noncombustible partitions to create office spaces, conference rooms, work rooms, men's and women's accessible shower areas, construction of two new mechanical shafts to extend from roof top units to the fourth floor, install new ceiling system and related lighting, new electrical, mechanical and plumbing work, miscellaneous related interior finishes, this building is fully fire sprinklered any alterations to the sprinkler system shall be maintained per NFPA #13 as regulated by the fire department. RmH
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/29/20089/29/20089/29/2008PPASS
DetailsForrest France
Fire alarm permit work passed inspection after on site repairs were completed including relocated in-ducts at the 6th floor and adjusted appliances on the 4th floor, as-built plans accepted, items on previous correction notice verified for compliance, inspection passed, permit finaled.
INSP-Alarm Testing9/26/20089/26/20089/26/2008PFAIL
DetailsTroy Cobbley
This inspection was for the 4th and 5th floors. Repair the inoperative fire smoke damper on the 4th floor. Provide as-builts as discussed.
INSP-Final Inspection9/24/20089/25/20089/25/2008AFAIL
DetailsForrest France
Field inspection for the 5th floor only completed today, noted several items in need of revision or adjustment. See 13 item correction notice left on site for a detailed list.
INSP-Alarm Testing9/18/20089/19/20089/19/2008PPART
DetailsTroy Cobbley
A temporary occupancy was given for the sixth floor with sam rogers permission until the vesda interconnections have been tested and the induct detectors have been correctly oriented as per sams and chris's telephone conversation.
INSP-Alarm Testing9/17/20089/18/20089/18/2008ADONE
DetailsTroy Cobbley
Todays inspection was just for the sixth floor. Horn/strobe placement and candella apppears to match the plans. One strobe as marked on the plans needs to be relocated 2' to the south to be within 15'-0" of the end of the corridor. We did not activate the audio/visuals. All of the heat pumps shut down when tested. The induct detectors are mounted half in and half out of the return duct openings. Per the installation guide they are to be placed a minumum six duct widths from the openings. Simplex stated that their engineers said it was ok to be installed that way. I verified with Stephanie that no such verification had been provided with this submittal. Simplex stated that they would provide this information as soon as possible. I told them to provide it to the plan reviewer. Todays testing was completed on that note.