Permit Information
Permit NumberFIR08-00533
StatusFinaled
Name PEAK ALARM
Site Address 4614 W STATE ST
Project NameCOLLISTER SHOPPING CTR
Customer Number 
ePlanReview 
Description
This fire alarm permit is to remove two tamper switches from an existing fire alarm control panel zone and connecting two new tamper switches in a separate location to that zone. This permit scope also includes adding a new flow switch to the existing water flow zone.
Associated building permit: BLD07-03079 (COLLISTER SHOPPING CENTER - BUILDING #200 - SOUTH MULTIPLE TENANT BUILDING - STOREFRONT, CANOPY, AND PARKING LOT REMODEL) (7-25-08) PLAN MODIFICATION TO CONSTRUCT A 1-HR FIRE SPRINKLER RISER ROOM WITH ACCESS DIRECTLY FROM THE EXTERIOR. This building is fire sprinklered for building area increase. To remodel the storefront and the canopy of Building #200 (South multiple tenant building). The parking lot will also be remodeled in conjunction with this permit. Work is to include new storefront glazing, new storefront glass doors, new parapets on existing exterior walls, new braces to the roof deck for new parapets, new exterior wall infills, new steel beams, new steel roof decking, exterior veneer brick, and new exterior stucco. The work is required to comply with the approved drawings, with the structural design, with the plan review report, and with all applicable codes. The fire sprinkler system is required to be maintained in compliance with NFPA 13 as regulated by the Fire Department. This is a shell only permit. It does NOT establish a Certificate of Occupancy for any tenant. CJW DRH07-00453
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/2/200810/3/200810/3/2008APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection9/29/200810/1/200810/1/2008PCANC
DetailsTroy Cobbley
Neither flow switch would activate the outside alarm bell.
INSP-Final Inspection9/5/20089/5/20089/5/2008PFAIL
DetailsTroy Cobbley
Provide updated map at the facp and provide an electric alarm bell.