Permit Information
Permit NumberFIR08-00569
StatusExpired
Name DEBEST FIRE PROTECTION
Site Address 301 N 29TH ST
Project NameWhittier Elementary
Customer Number 
ePlanReview 
Description
FIR OH Work Scope: Revised 08/29/08 - Modify the existing riser assembly by adding a new 2-1/2" back flow preventer with supervisory (tamper) switches and replace the existing (21) standard response upright sprinkler heads with new quick response upright sprinklers heads in order to use the quick response modifier rule as reflected in NFPA 13.11.2.3.2.3 so as to prove the required calculations and friction loss for the backflow preventer. The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIR-Aging Inspection1/3/20111/3/20111/10/2011 DONE
DetailsForrest France
FIR-Aging Inspection9/15/20109/15/20109/15/2010 NR
DetailsForrest France
FIR-Aging Inspection6/21/20106/21/20106/23/2010 DONE
DetailsForrest France
INSP-Final Inspection9/22/20089/23/20089/23/2008APART
DetailsForrest France
Scope of fire sprinkler work is complete, final pending forward flow test and control valve tamper switch supervision including the backflow shutoff valves.