INSP-Final Inspection | 2/6/2009 | 2/9/2009 | 2/10/2009 | A | PASS |
Forrest France
|
|
|
Corrections field verified, scope of fire sprinkler work finaled.
|
INSP-Final Inspection | 2/4/2009 | 2/5/2009 | 2/6/2009 | A | FAIL |
Forrest France
|
|
|
Noted three missing escutcheons at the new hard lid soffit, need to remove travel caps, one QR pendent has not been changed to match adjacent heads as noted during the previous inspection.
|
INSP-Final Inspection | 1/29/2009 | 1/29/2009 | 1/29/2009 | P | FAIL |
Forrest France
|
|
|
Three pendent heads at the meat dept. do not match response type with adjacent heads in the same fire area, also noted two heads to be adjusted to meet min. spacing req. Remainder of work scope completed okay.
|