Permit NumberFIR08-00763
StatusFinaled
Name ALARM STAR
Site Address 3858 N GARDEN CENTER WAY STE 301
Project NameGARDEN CENTER
Customer Number 
ePlanReview 
Description
4-22-11 CLARIFICATION: It was previously stated that this building has a voluntary manual system, however due to the occupant load being greater than 100 above the lowest level of exit discharge, this system is required. 12-31-08 SCOPE MODIFICATION: In-duct smoke detectors have been provided for fire/smoke damper operation.

This fire alarm permit is to install a new fire alarm system in a new building. This permit scope is to include a voluntary manual fire alarm system and required sprinkler system monitoring, elevator recall, and elevator shunt trip functions. The drawings do not indicate any HVAC control or monitoring functions.

Associated building permit: BLD08-00594 (THE TERTELING COMPANY, INC. - 3RD STORY) This building is fire sprinklered for code trade-offs. To construct a 6,330 square foot whole floor office tenant space on the 3rd story of a new 21,000 square foot 3 story building. Work is to include interior nonbearing walls, interior doors, suspended acoustical ceilings, gypsum board soffits, millwork, and finishes. The restrooms, drinking fountain, and service sink were installed under the shell permit (BLD07-03134). The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/27/20091/27/20091/27/2009PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing1/23/20091/26/20091/26/2009PFAIL
DetailsTroy Cobbley
All items tested ok except the second floor flow alarm was sent out as a second floor tamper. The first floor electrical room horn was changed to a horn strobe as I waited due to the horn being non temporal.