Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberFIR08-00771
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1253 N COLE RD
Project NameREDMONT OUTPATIENT SER
Customer Number 
ePlanReview 
Description
This fire alarm permit is to replace all the existing 4-wire notification devices with new, adding a NAC panel, adding a new pull station, and tying in to the existing FACP.

Associated building permit: BLD08-02067 (REDMONT OUTPATIENT) Remodel of 4,675 sq. ft. portion of existing 10,412 sq. ft. building to create a tenant space for Redmont Outpatient Services. Work includes select areas of interior demolition in preparation for new construction. New construction includes interior non-bearing walls to create this tenant space, five private offices, three conference rooms, a break room, accessible restrooms, waiting / reception and support areas, non-rated corridor and new exterior exit doors to serve the large conference room and adjoining areas. The large conference room, #115, is classified as an 'A3' occupancy due to occupant load greater than 50. Additions of two exterior exit doors, landings, clear floor space and hardware per 2006 IBC. Work includes upgrade of electrical, plumbing, mechanical, sprinkler and alarm system to meet tenant needs and for code compliance. Bi-level switching is provided in newly created rooms for energy code compliance. Hi-lo accessible drinking fountains, a service sink and specimen sampling / testing restroom facility are provided. This building is fully sprinklered for allowable area increase based on 1991 UBC, code at time of construction. drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/22/20091/23/20091/23/2009PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection1/21/20091/21/20091/21/2009PFAIL
DetailsTroy Cobbley
The interconnection between the new NAC panel and the existing FACP passed. What failed is that many of the new audio/visual devices are mounted too low. Two 110 cd strobes in the large open area on the north side of the building are mounted almost against building columns so they need to be relocated over so as to be unobstructed. A corridor on the south side has no notification installed and a device will need to be added. When this is done the system will need to be inspected.