Permit Information
Permit NumberFIR08-00779
StatusFinaled
Name ALARMCO
Site Address 1388 S ENTERTAINMENT AVE
Project NameTUCANOS BRAZILIAN GRILL
Customer Number 
ePlanReview 
Description
This fire alarm permit is to add duct detector and kitchen hood monitoring to an existing fire alarm panel.

Associated building permit: BLD08-01656 (TUCANOS BRAZILIAN GRILL) Build-out and finish of an 7,450 sq. ft. area with a 545 sq. ft. covered patio area (SHELL permit BLD08-00896) for use as a full service restaurant with kitchen, service, waiting and dining areas and to construct a new 369 sq. ft. mezzanine area for office and storage use, per reviewed plans, red-line notes on plans and all attached plan review comments and conditions of all reviewing agencies. Work includes construction of interior walls to create kitchen/service/grill areas, dining areas, fully accessible MEN'S & WOMEN'S restrooms and installation of millwork & finishes; installation of electrical light fixtures, controls & mechanical ductwork to meet energy code compliance; suspended ceiling grid system per CISCA 0-2; two (2) Type 1 grease hoods, grease duct exhaust systems with approved grease duct wrap assembly to create required shafts around grease ducts; installation of walk-in coolers and kitchen equipment; and electrical, mechanical, plumbing and fire suppression systems upgrade for compliance with current adopted codes and ordinances and to meet tenants needs. This building is fully sprinklered to NFPA 13 standards based on area of occupancy use group with alarm activation upon fire flow. The SHELL permit is required to be finaled with Letter of Compliance issued before or at same time as tenant final for occupancy. drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/9/20092/9/20092/9/2009PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection2/6/20092/6/20092/6/2009PFAIL
DetailsTroy Cobbley
The original panel was replaced after it was blown up due to high voltage backfeed from the ansul suppression system. The duct smoke detectors did not shut down the hvac units. The backflow preventor tamper switch needs to be on a separate zone which will cause modifications to the existing zone arrangement. As-builts are required but plan resubmittals are not. An updated map for the facp is required as well. The system will need to be retested once the zones have been redone.