Permit Number | FIR08-00784 |
Status | Finaled |
Name |
SIMPLEX GRINNELL
|
Site Address |
874 W BROAD ST
|
Project Name | LUNATIC FRINGE T.I. |
Customer Number | |
ePlanReview | |
Description |
This quick permit is to add a strobe only in a new bathroom and relocate an existing horn/strobe. The new strobe is being added to an existing notification circuit. It appears the calculations accomodate this new device, however the AH required are very close to the battery AH provided. Inspector to field verify the panel and battery capabilities are not exceeded. No written comments provided. Associated building permit: BLD08-02063 per Levi Hemmer is not providing a contractor registration number because he says he is exempt per Idaho State Code #54-5205/mls/10-7-08 **(Lunatic Fringe Salon)** To remodel an existing 1804 sq ft tenant space for new hair salon per approved plans. Work to include, construction of one new handicap accessible restroom, installation of five new shampoo sinks, new work stations, installation of new track lighting, this building is fully fire sprinkled any alterations to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed and maintained per NFPA #13 Rmh
|