Permit Information
Permit NumberFIR08-00785
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1253 N COLE RD
Project NameREDMONT OUTPATIENT SER
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of adding and relocating heads to accommodate new wall configurations.

Associated building permit BLD08-02067 - (REDMONT OUTPATIENT) Remodel of 4,675 sq. ft. portion of existing 10,412 sq. ft. building to create a tenant space for Redmont Outpatient Services. Work includes select areas of interior demolition in preparation for new construction. New construction includes interior non-bearing walls to create this tenant space, five private offices, three conference rooms, a break room, accessible restrooms, waiting / reception and support areas, non-rated corridor and new exterior exit doors to serve the large conference room and adjoining areas. The large conference room, #115, is classified as an 'A3' occupancy due to occupant load greater than 50. Additions of two exterior exit doors, landings, clear floor space and hardware per 2006 IBC. Work includes upgrade of electrical, plumbing, mechanical, sprinkler and alarm system to meet tenant needs and for code compliance. Bi-level switching is provided in newly created rooms for energy code compliance. Hi-lo accessible drinking fountains, a service sink and specimen sampling / testing restroom facility are provided. This building is fully sprinklered for allowable area increase based on 1991 UBC, code at time of construction.

System Design History
The existing sprinkler system appears to be designed for light hazard construction 225SF. The system modifications are designed for light hazard 225SF.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/22/20091/23/20091/23/2009APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection1/21/20091/21/20091/21/2009PFAIL
DetailsTroy Cobbley
The approved fire sprinkler plans show many rooms where the modified sprinkler pendants are to be changed to a quick responce type. The sprinkler heads installed are of the standard responce type.
INSP-Sprinkler Rough-in/Hydro12/18/200812/19/200812/19/2008APART
DetailsForrest France
Modifications for the exitsing system per the scope of permit work are good for cover at the drop ceilings. Need to provide a current annual inspection for the existing system and riser prior to final occupancy approval.