Permit Information
Permit NumberFIR08-00791
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1388 S ENTERTAINMENT AVE
Project NameTUCANOS BRAZILIAN GRILL
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of adding and relocating heads to accommodate new wall and ceiling configurations.

Associated building permit BLD08-00791 (TUCANOS BRAZILIAN GRILL) Build-out and finish of an 7,450 sq. ft. area with a 545 sq. ft. covered patio area (SHELL permit BLD08-00896) for use as a full service restaurant with kitchen, service, waiting and dining areas and to construct a new 369 sq. ft. mezzanine area for office and storage use, per reviewed plans, red-line notes on plans and all attached plan review comments and conditions of all reviewing agencies. Work includes construction of interior walls to create kitchen/service/grill areas, dining areas, fully accessible MEN'S & WOMEN'S restrooms and installation of millwork & finishes; installation of electrical light fixtures, controls & mechanical ductwork to meet energy code compliance; suspended ceiling grid system per CISCA 0-2; two (2) Type 1 grease hoods, grease duct exhaust systems with approved grease duct wrap assembly to create required shafts around grease ducts; installation of walk-in coolers and kitchen equipment; and electrical, mechanical, plumbing and fire supression systems upgrade for compliance with current adopted codes and ordinances and to meet tenants needs. This building is fully sprinklered to NFPA 13 standards based on area of occupancy use group with alarm activation upon fire flow. The SHELL permit is required to be finaled with Letter of Compliance issued before or at same time as tenant final for occupancy. drs

System Design History
The original fire sprinklers system was reported designed for .10/1500 Light Hazard with heads spaced at 130SF.

The alterations will be based on .10/1500 Light Hazard for the seating area with SSP up to 225 SF and EC up to 400SF. The kitchen area will be based upon on Ordinary Hazard Group I with a maximum spacing of 130 SF
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/9/20092/9/20092/9/2009PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection2/6/20092/6/20092/6/2009PFAIL
DetailsTroy Cobbley
Not all of the sprinkler work is complete. Forward flush passed. Tim Frost is ok with the relocation of the PIV from the landscape/island to the exterior wall. The electric alarm bell is missing.
INSP-Sprinkler Rough-in2/5/20092/5/20092/5/2009PPASS
DetailsTroy Cobbley
The remaining piping can be covered. I noted one sprinkler pendant at the intermediate stair landing is overspaced from the north wall. Also per the builder insulation will be utilized above the ceiling in front of the public restrooms.
INSP-Sprinkler Rough-in1/6/20091/6/20091/7/2009PPASS
DetailsTroy Cobbley
The sprinkler piping above the hardlid soffits is ok to cover. I spoke to Brian Johnson and to Andy, the builder, about the PIV that was shown to be installed on the overhead sprinkler plans has not been installed. Per the separate underground permit FIR08-00514 no PIV was being installed. The PIV needs to be installed, a wall PIV approved by the city of boise installed or the one hour room with exterior access provided. Brian stated that he would contact me with a solution.
INSP-Sprinkler Rough-in/Hydro12/23/200812/24/200812/24/2008APART
DetailsForrest France
Fire sprinkler piping at both the womens and mens restrooms only are approved for cover at this time.