Permit Information
Permit NumberFIR09-00008
StatusFinaled
Name CURTIS FIRE SPRINKLER SERVICE INC
Site Address 2480 S STARLITE LN
Project NameYagues Residence
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of a new residential NFPA 13D sprinkler system in a new two level house.

This project is for the construction of a new 2-story single family dwelling. The lower level will have 1,280s.f. of living area along with a three car garage of 875s.f. The upper and main level will have 2,853 s.f. along with 693s.f. of above grade balcony area that includes an 84s.f. covered entry area. The exterior balcony and stairways are using cable guardrails and must meet the requirements of the Building Division Policy of March 20, 2008 (attached). R-1C ok per Sue Cummings per notes restricting lower level cannot have a kitchen, under counter refer only and there is not to be a 220 receptacle for a range. Separate electrical, plumbing and mechanical permits are required. ESC08-00866 permit is already in force for the grading permit MIS08-00157. ESC plans were approved through these permits also. The grading and drainage must be certified by an approval letter from the design engineer of record to Public Works prior to issuance of a building dept final approval. All per the approved plans as marked engineering calculations and the engineer's details; Energy code component method along with the plan review notes. Pep
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/24/20094/24/20094/24/2009PPASS
DetailsForrest France
Fire sprinkler permit work approved for final per T. Frost.
INSP-Supply line flush4/23/20094/24/20094/24/2009PPASS
DetailsForrest France
UG fire supply line flush completed acceptable per T. Frost.
INSP-Final Inspection4/23/20094/23/20094/23/2009PNR
DetailsForrest France
Scheduled by a contractor via Hello! on 4/23/2009 at 7:43:09 AM. Contact: ###-####.
INSP-Supply line flush4/23/20094/23/20094/23/2009PNR
DetailsForrest France
Pending coordination with united water for supply line flush.
INSP-Sprinkler Rough-in/Hydro2/9/20092/9/20092/10/2009APART
DetailsForrest France
Overhead fire sprinkler installation okayed for cover.
INSP-Sprinkler Rough-in/Hydro2/5/20092/5/20092/5/2009PPART
DetailsForrest France
Noted correction items have been repaired with the exception of inadequate tenting at three locations-explained to contractor on site where adjustments should be made. Will need to verify prior to sheetrock cover.
INSP-Sprinkler Rough-in/Hydro2/3/20092/4/20092/4/2009AFAIL
DetailsForrest France
See approved plan set for red-line annotations indicating deficient items including locations where heads are too close to light fixture junction boxes and may become obstructed due to surface mounted lights, ordinary temp. heads must be at least 5' from the front of the fireplace, noted one head too close to a heat diffuser, pendent head at a bedroom is too close to a ceiling fan (maintain min. 3' from the down rod), the CPVC riser must be installed per listing, noted several areas lacking correct tenting for cold cavity protection, missing nailer plates at both main level risers, installation is not approved for cover at this time.