INSP-Final Inspection | 4/24/2009 | 4/24/2009 | 4/24/2009 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit work approved for final per T. Frost.
|
INSP-Supply line flush | 4/23/2009 | 4/24/2009 | 4/24/2009 | P | PASS |
Forrest France
|
|
|
UG fire supply line flush completed acceptable per T. Frost.
|
INSP-Final Inspection | 4/23/2009 | 4/23/2009 | 4/23/2009 | P | NR |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 4/23/2009 at 7:43:09 AM. Contact: ###-####.
|
INSP-Supply line flush | 4/23/2009 | 4/23/2009 | 4/23/2009 | P | NR |
Forrest France
|
|
|
Pending coordination with united water for supply line flush.
|
INSP-Sprinkler Rough-in/Hydro | 2/9/2009 | 2/9/2009 | 2/10/2009 | A | PART |
Forrest France
|
|
|
Overhead fire sprinkler installation okayed for cover.
|
INSP-Sprinkler Rough-in/Hydro | 2/5/2009 | 2/5/2009 | 2/5/2009 | P | PART |
Forrest France
|
|
|
Noted correction items have been repaired with the exception of inadequate tenting at three locations-explained to contractor on site where adjustments should be made. Will need to verify prior to sheetrock cover.
|
INSP-Sprinkler Rough-in/Hydro | 2/3/2009 | 2/4/2009 | 2/4/2009 | A | FAIL |
Forrest France
|
|
|
See approved plan set for red-line annotations indicating deficient items including locations where heads are too close to light fixture junction boxes and may become obstructed due to surface mounted lights, ordinary temp. heads must be at least 5' from the front of the fireplace, noted one head too close to a heat diffuser, pendent head at a bedroom is too close to a ceiling fan (maintain min. 3' from the down rod), the CPVC riser must be installed per listing, noted several areas lacking correct tenting for cold cavity protection, missing nailer plates at both main level risers, installation is not approved for cover at this time.
|