Permit NumberFIR09-00060
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1150 N CURTIS RD
Project NameBUREAU OF RECLAMATION 1ST FLR
Customer Number 
ePlanReview 
Description
This quick permit scope is to add five pull stations and relocate three pull stations to an existing fire alarm system. Manual pull stations must be mounted per IFC 2006 and NFPA 72 requirements. There are no written comments. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/18/20108/18/20108/18/2010PPASS
DetailsTroy Cobbley
Permit finaled.
FIR-Aging Inspection8/18/20108/18/20108/18/2010 PASS
DetailsTroy Cobbley
INSP-Final Inspection4/22/20104/23/20104/23/2010AFAIL
DetailsTroy Cobbley
Testing is complete and the pull stations functioned correctly. As-builts are needed since all but one of the manual pull stations shown to be relocated actually remained and is functional. The single pull station was shown to be relocated but was non-functional and was removed while I waited. Permit can be finaled when the as-builts are received.
FIR-Aging Inspection5/4/20095/4/20095/7/2009 NR
DetailsTroy Cobbley
Work in progress per Charlie Bayne. He stated work to be completed by the end of this month.