Permit Information
Permit NumberFIR09-00098
StatusFinaled
Name BIG M ELECTRIC INC
Site Address 4892 N CLOVERDALE RD
Project NameBoise Retirement Residence
Customer Number 
ePlanReview 
Description
BLDG C PLAN MODIFICATION 10-19-09:
This plan modification includes providing modules for synchronizing the audibility between the room notification devices and the building notification devices. This modification also includes implementing as-built devices and previous plan review comments.

This fire alarm permit is to provide a new fire alarm system in a new building. Permit scope includes automatic smoke detection system with full notification, monitoring for HVAC, dampers, and sprinkler system, Elevator recall functions, smoke shutters in the 3rd floor atrium, fire doors, a fire pump, kitchen hood suppression system monitoring, and an emergency generator.

Associated building permit: BLD08-02082 (BOISE RETIREMENT RESIDENCE - BLDG C - WEST SECTION) To construct a new 29 unit 23,254 square foot, three story, I-1, non state licensed, residential care, assisted living facility where all residence will be capable of responding to an emergency situation without physical assistance. This building to be fully fire sprinklered with an NFPA 13-R system as required by the occupancy. This area is separated from the center building (Section A) by a 2-hr. fire wall. Note: This project was reviewed by ICC for energy, structural, nonstructural and accessibility requirements for code compliance. (23 units are less than 800 sq.ft. and 6 units are greater than 800 sq.ft.)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/20/200910/20/200910/20/2009PPASS
DetailsTroy Cobbley
The syncing of the handicap rooms a/v's has been addressed. The placement and testing of the atrium smoke detectors has been addressed. Permit finaled.
INSP-Alarm Testing5/13/20095/13/20095/14/2009PPASS
DetailsTroy Cobbley
The fire alarm rough-in for the first and second floors of building C passed.
INSP-Alarm Testing5/7/20095/7/20095/7/2009PPASS
DetailsTroy Cobbley
Today's inspection was a rough-in inspection of 3rd floor building C which passed.