INSP-Final Inspection | 5/21/2009 | 5/22/2009 | 5/22/2009 | A | PASS |
Forrest France
|
|
|
All corrections per last inspection are finished, fire sprinkler permit finaled.
|
INSP-Final Inspection | 5/19/2009 | 5/20/2009 | 5/20/2009 | A | FAIL |
Troy Cobbley
|
|
|
There is a Storage Room 130 as shown on the approved building plans that has wood racks recently built. The sprinkler pendants exceed the maximum 130 sq. ft. per head allowed for ordinary hazard which this room would be considered. As-builts are required but resubmittals won't be. Also the minimum 18" clearance is not available due to the top shelf of these racks. Per discussion with the property manager the top rack will be removed.
|
INSP-Final Inspection | 5/19/2009 | 5/20/2009 | 5/20/2009 | P | DONE |
Forrest France
|
|
|
Duplicate inspection request.
|
INSP-Final Inspection | 4/29/2009 | 4/30/2009 | 4/30/2009 | A | NR |
Forrest France
|
|
|
Missing field ceiling tiles at several locations, final pending completion of this work.
|
INSP-Sprinkler Rough-in/Hydro | 4/7/2009 | 4/8/2009 | 4/8/2009 | P | PART |
Forrest France
|
|
|
Overhead changes per the scope of work indicated are approved for cover at the drop ceilings.
|