INSP-Final Inspection | 9/29/2009 | 9/29/2009 | 9/29/2009 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Final Inspection | 9/24/2009 | 9/25/2009 | 9/25/2009 | P | PART |
Forrest France
|
|
|
See inspection comments per T. Frost.
|
INSP-Final Inspection | 9/22/2009 | 9/22/2009 | 9/25/2009 | P | FAIL |
Forrest France
|
|
|
Inspection items for final per notes 9/22 include new batteries at the main FACP, post a current map with accurate floorplan and zone descriptors, install and test a missing smoke detector at the first floor vestibule, provide list of signals recieved at offsite monitoring from this day's testing, new/existing horn strobes are not in sync- second floor elevator lobby and corridors.
|
INSP-Alarm Testing | 8/27/2009 | 8/28/2009 | 8/28/2009 | P | PART |
Forrest France
|
|
|
See inspection comments per T. Frost for alarm work tested today. Also note; Effective 8/31/2009 until 9/30/2009 - Temporary occupancy is permitted, within the existing portions of the building only, based on the following conditions. Access to the new addition construction areas shall be secured from non construction personnel. All life safety, fire protection sprinkler and alarm systems, shall be fully installed, functional, and monitored in occupied areas. All inspection correction items shall be completed prior to the issuance of final occupancy.
|
FIR-Aging Inspection | 6/30/2009 | 6/30/2009 | 6/30/2009 | | DONE |
Forrest France
|
|
|
Work in progress, construction underway.
|