Permit Information
Permit NumberFIR09-00216
StatusFinaled
Name TRI STATE ELECTRIC
Site Address 851 W FRONT ST Unit: 1403
Project NameTHE ASPEN - UNIT 1403
Customer Number 
ePlanReview 
Description
This fire alarm permit is to provide speakers, speaker/strobes, and single/multi-station smoke alarms as a tenant improvement for a condo. These devices are an extension of the building voice evacuation system.

Associated building permit: BLD08-01376 (THE ASPEN - RESIDENTIAL UNIT 1403) Fire sprinklers required because this building is a high-rise. To create a 1,148 square foot dwelling unit on the 14th story of a new high-rise building. The 1-hr corridor on the 14th story will be constructed in conjunction with this permit. Work is to include 1-hr fire-resistance-rated tenant demising walls, 1-hr fire-resistance-rated corridor, interior nonbearing walls, suspended gypsum board ceilings, millwork, and finishes. This dwelling unit is required to comply with ICC/ANSI A117.1-2003 Section 1004 as a Type B dwelling unit. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/24/20099/24/20099/24/2009PPASS
DetailsForrest France
Fire alarm reinspection passed, transfer grill <3' from SA okayed.
INSP-Final Inspection9/15/20099/21/20099/22/2009AFAIL
DetailsForrest France
Smoke alarms need to be located away from supply or return air diffusers to avoid a delay in operation a min. of 3' per NFPA 72 -see fire code review notes item #3. Notification tested okay.