Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR09-00248
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 510 W HALE ST
Project NameICONIC VILLAGE Bldg J
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of adding a new 13R sprinkler system to existing aparment.

(Building J - 510 W. Hale St. units 100 & 200) This project is to convert an existing two bedroom, one bathroom, two story apartment unit into (2) one bedroom, one bathroom units. Work to include: Minor demolition, new non-load bearing partitions, electrical modifications, paint and floor finishes, new automatic fire sprinkler system installed throughout in accordance with NFPA 13R, new bathroom (first floor unit), new kitchenette (second floor unit), and a sixteen square foot addition for the fire riser room will be added to the building. A phased upgrade agreement is approved and attached for the automatic sprinkler system improvements. All other alterations related to this building are permitted under BLD09-00457, and BLD09-00459. All work per approved plans and attached plan review report. The occupant load calculated under this permit is only for the units being remodeled/added. DRH08-00152, CUP08-00073, and CZC09-00047 per planning and zoning. **SRZ**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/14/20097/15/20097/15/2009PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro7/5/20097/6/20097/6/2009PPASS
DetailsTroy Cobbley
overhead hydro bldg J passed.
INSP-Sprinkler Rough-in/Hydro6/18/20096/19/20096/19/2009PPART
DetailsForrest France
Unit 514 Building J okayed for cover, noted missing SW head at the understair closet.
INSP-Sprinkler Rough-in6/4/20096/4/20096/4/2009APART
DetailsForrest France
See approved plans for 1st and 2nd floors okayed for cover in building J units 510 and 512.
INSP-Sprinkler Rough-in6/2/20096/3/20096/3/2009ANH
DetailsForrest France
We respectfully request a partial rough-to-cover for Bld. J at the Iconic Apartments. Please call Scott 1 HOUR BEFORE inspection. **INSPECTORS NOTE**: Pease list contact phone number on inspection request. Niether approved set of sprinkler plans or contractor could be located on site, noted missing coverage at one location unit 512.

Thank you. Phone #: ###-#### Internet Inspection Request from: Trent Bice
INSP-Sprinkler Rough-in/Hydro5/21/20095/22/20095/25/2009AFAIL
DetailsForrest France
UG supply line hydrostatic test failed due to pressure loss at the guage per inspection completed by T. Frost.
INSP-Sprinkler Rough-in5/19/20095/19/20095/19/2009PPASS
DetailsTroy Cobbley
The 2" underground supply piping is ok to cover. The contractor did not have the original approved plans, just copies, on site. I let him know those would be needed at the next inspection.