Permit Information
Permit NumberFIR09-00255
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 502 W HALE ST
Project NameICONIC VILLAGE
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of adding a new 13R sprinkler system to existing apartment.

(Building 'N' - 502 W. Hale St. units 100 & 200) This project is to convert an existing two bedroom, one bathroom, two story apartment unit into (2) one bedroom, one bathroom units. Work to include: Minor demolition, new non-load bearing partitions, electrical modifications, paint and floor finishes, new automatic fire sprinkler system installed throughout in accordance with NFPA 13R, new bathroom (first floor unit), new kitchenette (second floor unit), and a sixteen square foot addition for the fire riser room will be added to the building. A phased upgrade agreement is approved and attached for the automatic sprinkler system improvements. All other alterations related to this building are permitted under BLD09-00449, BLD09-00451, and BLD09-00453. All work per approved plans and attached plan review report. The occupant load calculated under this permit is only for the units being remodeled/added. DRH08-00152, CUP08-00073, and CZC09-00047 per planning and zoning. **SRZ**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/5/20098/7/20098/7/2009APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection8/5/20098/7/20098/7/2009APASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in/Hydro8/7/20098/7/20098/7/2009PPASS
DetailsTroy Cobbley
Above ground hydro test passed
INSP-Sprinkler Rough-in/Hydro7/15/20097/16/20097/16/2009APART
DetailsTroy Cobbley
Rough to cover apartment 502 is passed after the pendants in the upstairs apartment were spaced correctly. The problem is the repair work is leaking so the hydro test failed and will need to be rescheduled.
INSP-Sprinkler Rough-in/Hydro7/15/20097/15/20097/15/2009ACANC
DetailsTroy Cobbley
duplicate inspection
INSP-Sprinkler Rough-in/Hydro7/14/20097/14/20097/15/2009PFAIL
DetailsTroy Cobbley
above ground hydro failed. No rough in inspection was performed
INSP-Supply line flush6/5/20096/8/20096/8/2009PPART
DetailsForrest France
UG fire supply line flushing completed okay.
INSP-Sprinkler Rough-in6/4/20096/4/20096/4/2009PPART
DetailsForrest France
UG fire supply line hydrostatic retest passed.
INSP-Sprinkler Rough-in/Hydro5/21/20095/22/20095/25/2009AFAIL
DetailsForrest France
UG supply line hydrostatic test failed due to pressure loss at the guage per inspection completed by T. Frost.
INSP-Sprinkler Rough-in5/18/20095/19/20095/19/2009APASS
DetailsTroy Cobbley
The 2" underground supply piping is ok to cover. The contractor did not have the original approved plans, just copies, on site. I let him know those would be needed at the next inspection.