Permit NumberFIR09-00365
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 11311 W CHINDEN BLVD
Project NameHP BLDG 3
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of installing a new wet tree system into an existing mechanical area around new mechanical equipment. The facility has a pump and tank The design is based on Ordinary Hazard Group II with SSU SR sprinklers

(HEWLETT PACKARD BLDG #3) Remodel to extend an industrial equipment platform out under the existing roofline to provide additional mechanical space for an upgrade to the HVAC system per approved plans. Work to include..
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/6/200910/7/200910/7/2009APASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro10/6/200910/6/200910/6/2009PPASS
DetailsTroy Cobbley
Rough-in and hydro test passed.
INSP-Final Inspection9/14/20099/15/20099/15/2009AFAIL
DetailsForrest France
Need plan resubmittals due to significant changes in field installation and calc areas from what is shown on stamped drawings, also need to complete a hydrostatic test of the new piping and sprinklers.
FIR-Aging Inspection9/8/20099/8/20099/10/2009 NR
DetailsTroy Cobbley
work is in progress per jeff