Permit Information
Permit NumberFIR09-00375
StatusFinaled
Name ALARMCO
Site Address 621 S 17TH ST
Project NamePOWERHOUSE EVENT CENTER
Customer Number 
ePlanReview 
Description
This fire alarm permit is to replace the DACT (phone lines) functions with RF Radio for monitoring. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/21/20122/23/20122/24/2012PPASS
DetailsForrest France
Fire alarm permit finaled. Inspection passed.
FIR-Aging Inspection2/21/20122/21/20122/21/2012 DONE
DetailsForrest France
Contractor to schedule final for 2/23/12 PM
FIR-Aging Inspection11/1/201111/1/201111/1/2011 FAIL
DetailsForrest France
FIR-Aging Inspection7/8/20117/8/20117/8/2011 FAIL
DetailsForrest France
Failed inspection 2/23.
FIR-Aging Inspection3/30/20113/30/20113/30/2011PPEND
DetailsForrest France
Final pending repairs and scheduled retest.
INSP-Final Inspection2/22/20112/22/20112/23/2011PFAIL
DetailsForrest France
Netcon rating could not be verified on site, trouble signal was sent but not recieved offsite, exposed wiring at power supply. No further items checked, inspection concluded.
INSP-Final Inspection2/11/20112/11/20112/14/2011PNH
DetailsForrest France
Please call Rich at ###-#### with inspection time. Phone #: ###-#### >> Inspection requested via web by Lori Brungardt
FIR-Aging Inspection2/1/20112/1/20112/1/2011 FAIL
DetailsForrest France
FIR-Aging Inspection11/30/201011/30/201012/2/2010 FAIL
DetailsForrest France
Need site inspection request
FIR-Aging Inspection9/28/20109/28/201010/6/2010 FAIL
DetailsForrest France
Need inspection request for permit final by contractor.
FIR-Aging Inspection9/17/20099/17/20099/17/2009 DONE
DetailsForrest France
Work in progress