Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR09-00418
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1914 S BROADWAY AVE
Project NameGarfield Elementary
Customer Number 
ePlanReview 
Description
This fire alarm permit is to provide a new 4010 panel for elevator recall functions. This permit scope to include initiating devices for the control and monitoring of elevator recall, elevator fireman's hat light functions, smoke detectors in lobbies, as well as smoke and heat detectors in the elevator machine room and elevator shaft. Notification devices are not part of this permit scope.

Associated building permit: BLD09-00616 (GARFIELD ELEMENTARY SCHOOL - RAMP AND ELEVATOR ADDITIONS) Only the basement of this building is fire sprinklered. To construct an exterior concrete ramp and an interior elevator shaft and elevator to serve an existing elementary school. An existing basement stairway and an existing 2nd story stairway will be eliminated. An existing 1st story stairway will be replaced with a new stairway, about 2 feet narrower than the old one. The new elevator will have 5 stops (basement, lower 1st story, upper 1st story, lower 2nd story, and upper 2nd story). For the exterior concrete ramp, work is to include concrete footings, concrete retaining walls, concrete slabs, metal guards, and metal handrails. For the interior elevator, work is to include a masonry shaft for the elevator, a 1-hr elevator machine room, and smoke control on the elevator doors (the elevator doors will open into existing 1-hr corridors). The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. **CJW**

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/4/20101/4/20101/5/2010PPASS
DetailsForrest France
Existing fire sprinkler riser main control valve does not require electrical tamper supervision per Mark Senteno. Remainder of elevator recall functions tested okay. Fire alarm permit finaled.
INSP-Final Inspection12/29/200912/30/200912/30/2009PCANC
DetailsTroy Cobbley
Cancelled due to time constraints.
INSP-Final Inspection12/7/200912/8/200912/9/2009PNR
DetailsForrest France
Pending building fire code review note item #21 regarding IFC 903.4 sprinkler monitoring and alarms.
INSP-Conference12/7/200912/7/200912/7/2009PDONE
DetailsForrest France
Regarding site inspection request for final 12/8 PM.
INSP-Conference11/3/200911/3/200911/3/2009ADONE
DetailsForrest France
Regarding fire code review notes items.
FIR-Aging Inspection10/15/200910/15/200910/20/2009 DEFR
DetailsForrest France
In progress