Permit Information
Permit NumberFIR09-00422
StatusFinaled
Name CONSOLIDATED FIRE TECH
Site Address 9134 W BLACKEAGLE DR
Project NameUSDA Wildlife Services
Customer Number 
ePlanReview 
Description
Quick Permit
Drop 3 sprinklers from the above sprinkler lines into new offices. There will be above and below protection therefore hydraulics are not required.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/11/200911/12/200911/12/2009APASS
DetailsTroy Cobbley
Permit finaled. Deficiencies corrected.
INSP-Final Inspection10/27/200910/27/200910/27/2009PFAIL
DetailsTroy Cobbley
Remove the protective caps from the pendant sprinklers per NFPA 13 - 8.3.1.5. Provide intermediate temperature pendant per NFPA 13 - Table 8.3.2.5 (a) for the pendant in necropsy room. Two pendants are nto allowed off of the same 1" outlet unless specific requirements of NFPA 13 are met. The plans do not show these requirements. The plans do not show this piping arrangement. The plans show separate outlets for each drop.