INSP-Final Inspection | 11/11/2009 | 11/12/2009 | 11/12/2009 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. Deficiencies corrected.
|
INSP-Final Inspection | 10/27/2009 | 10/27/2009 | 10/27/2009 | P | FAIL |
Troy Cobbley
|
|
|
Remove the protective caps from the pendant sprinklers per NFPA 13 - 8.3.1.5. Provide intermediate temperature pendant per NFPA 13 - Table 8.3.2.5 (a) for the pendant in necropsy room. Two pendants are nto allowed off of the same 1" outlet unless specific requirements of NFPA 13 are met. The plans do not show these requirements. The plans do not show this piping arrangement. The plans show separate outlets for each drop.
|