INSP-Final Inspection | 2/5/2010 | 2/8/2010 | 2/8/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 2/4/2010 | 2/5/2010 | 2/5/2010 | P | FAIL |
Troy Cobbley
|
|
|
Provide forward flow test of backflow, provide certification of the backflow, provide NFPA 25, provide head wrench, provide service tag on riser and provide signage at the aux. drain on the north wall. The interconnection with the fire alarm panel tested ok.
|
INSP-Sprinkler Rough-in/Hydro | 1/11/2010 | 1/12/2010 | 1/12/2010 | A | PASS |
Troy Cobbley
|
|
|
The overhead hydro test passed.
|
INSP-Sprinkler Rough-in/Hydro | 1/6/2010 | 1/7/2010 | 1/7/2010 | A | FAIL |
Troy Cobbley
|
|
|
The overhead hydro test was performed twice today and failed twice.
|
INSP-Sprinkler Rough-in/Hydro | 11/10/2009 | 11/12/2009 | 11/12/2009 | A | PASS |
Troy Cobbley
|
|
|
All of the sprinkler piping can be covered except in the show room area.
|
INSP-Sprinkler Rough-in/Hydro | 10/22/2009 | 10/23/2009 | 10/23/2009 | A | PASS |
Troy Cobbley
|
|
|
Rough-in inspection mostly passed. I noted one retaining strap missing, T-bar was not installed and will require a separate inspection and the showroom piping was not accessible for inspection. The hardlid areas are ok for cover.
|
INSP-Supply line flush | 10/22/2009 | 10/22/2009 | 10/22/2009 | P | CANC |
Troy Cobbley
|
|
|
The wrong permit number was called in for the underground flush.
|