INSP-Final Inspection | 3/10/2010 | 3/10/2010 | 3/12/2010 | P | PASS |
Forrest France
|
|
|
Previous C/N items field verified for completion, fire sprinkler permit finaled.
|
INSP-Final Inspection | 3/8/2010 | 3/9/2010 | 3/9/2010 | A | PART |
Forrest France
|
|
|
Permit work okay for final pending plan modification for upright protection only at this time in room 319, installation of ceiling tile for sprinkler heads at three locations, missing two 401 style canopies and one semi-recessed.
|
INSP-Final Inspection | 3/3/2010 | 3/3/2010 | 3/3/2010 | P | NR |
Forrest France
|
|
|
Exam room 319 missing drop sprinklers, escutcheons at some areas are not yet installed.
|
INSP-Sprinkler Rough-in/Hydro | 2/16/2010 | 2/16/2010 | 2/16/2010 | A | PART |
Forrest France
|
|
|
See plans for locations okayed for cover to date.
|
INSP-Sprinkler Rough-in | 2/2/2010 | 2/3/2010 | 2/3/2010 | A | PART |
Forrest France
|
|
|
Overhead fire sprinkler work is approved for cover at the drop ceilings with the exception of three areas as marked on approved plans, noted one missing head at the roof access hatch closet.
|
INSP-Sprinkler Rough-in | 11/6/2009 | 11/6/2009 | 11/10/2009 | P | PART |
Forrest France
|
|
|
See notes dated 11/4
|
INSP-Sprinkler Rough-in | 11/4/2009 | 11/4/2009 | 11/4/2009 | P | PART |
Forrest France
|
|
|
Inspection at overhead upright protection completed okay with the exception of one head (incorrect type) to be replaced and an unprotected pocket at the west side of the tenant space to be filled with non-combustible insulation to meet the allowed exception or provided with sprinklers as discussed.
|