Permit Information
Permit NumberFIR09-00510
StatusExpired
Name GUARDIAN ALARM SYSTEMS LLC
Site Address 1200 N MILWAUKEE ST
Project NameTHE HOME DEPOT-FA REPLACEMENT
Customer Number 
ePlanReview 
Description
This fire alarm permit is to replace an existing fire alarm system with new. Permit scope to include a full manual system, notification, sprinkler system monitoring (there are multiple wet and dry systems), HVAC shutdown, evaporator cooler shutdown, and fire pump monitoring. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Expired  1/23/2020 DONE
DetailsScott Arellano
This permit was DOC-Finaled by Scott Arellano on 4/7/2017 but the status was never changed in the system.
FIR-Aging Inspection5/13/20195/13/20195/13/2019 CANC
DetailsTroy Cobbley
FIR-Aging Inspection12/11/201712/11/201712/14/2017 NR
DetailsTroy Cobbley
Waiting for the contractor to schedule the work
FIR-Aging Inspection7/26/20177/26/20177/26/2017 NR
DetailsTroy Cobbley
Waiting for contractor to schedule work
FIR-Aging Inspection3/31/20173/31/20174/7/2017 PASS
DetailsScott Arellano
INSP-Final Inspection4/7/20174/7/20174/7/2017PPASS
DetailsScott Arellano
DOC - Permit Finaled4/7/20174/7/20174/7/2017PPASS
DetailsScott Arellano
FIR-Aging Inspection11/4/201611/4/201611/4/2016 CANC
DetailsTroy Cobbley
FIR-Aging Inspection7/27/20167/27/20167/27/2016 NR
DetailsTroy Cobbley
I spoke to Matt and he is going to follow up on project status
FIR-Aging Inspection10/15/201410/15/201410/15/2014 CANC
DetailsTroy Cobbley
FIR-Aging Inspection7/16/20147/16/20147/16/2014 CANC
DetailsTroy Cobbley
FIR-Aging Inspection12/13/201312/13/201312/17/2013 DONE
DetailsTroy Cobbley
I spoke to Matt about getting a final inspection for this project.
FIR-Aging Inspection7/18/20137/18/20137/18/2013 NR
DetailsTroy Cobbley
Work is in progress
FIR-Aging Inspection4/18/20134/18/20134/25/2013 NR
DetailsTroy Cobbley
work is in progress
INSP-Conference1/17/20131/17/20131/17/2013PDONE
DetailsTroy Cobbley
Went over details to final this project with Matt Casey. and with the onsite store manager Alan. It appears plan modifications will be required.
INSP-Conference1/9/20131/9/20131/9/2013PDONE
DetailsTroy Cobbley
I stopped at the store and spoke to the manager and later spoke to Josh on the phone about the job status and the need to move forward. Later in the day I also received a phone call from Home Depot corporate in Georgia and spoke to them about the same issue.
FIR-Aging Inspection1/8/20131/8/20131/9/2013 NR
DetailsTroy Cobbley
wip
FIR-Aging Inspection10/8/201210/8/201210/10/2012 NR
DetailsTroy Cobbley
I spoke to Matt and he is going to get me the contact information for Consolidated Fire.
FIR-Aging Inspection6/20/20126/20/20126/20/2012 NR
DetailsTroy Cobbley
Per Matt this project is slowing moving along.
FIR-Aging Inspection2/8/20122/8/20122/8/2012 NR
DetailsTroy Cobbley
Per matt casey issues are being worked out with the owner.
FIR-Aging Inspection10/21/201110/21/201110/21/2011 DONE
DetailsTroy Cobbley
Stephanie and Scott are following up with owner on status of project.
FIR-Aging Inspection1/5/20111/5/20111/12/2011 NR
DetailsTroy Cobbley
Matt is waiting on a change order for this project.
INSP-Alarm Testing10/30/200910/30/200910/30/2009PPASS
DetailsTroy Cobbley
The city approved drawings were found. See the city approved drawings, notification sheet, for the list of remaining items/corrections needed.
INSP-Alarm Testing10/28/200910/29/200910/29/2009ADONE
DetailsTroy Cobbley
The inspection today included verification of the phone line monitoring, NAC panel interconnection/trouble monitoring, and tamper/flow switch monitoring as marked on the plans. The job site copy of the plans was not on site. We found an anti-freeze system with three unsupervised control valves in the north east corner of the building that needs its annual inspection and the valves electrically monitored. No other items have been tested.