Permit Information
Permit NumberFIR09-00536
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1507 N 28TH ST
Project NameLOWELL ELEMENTARY SCHOOL
Customer Number 
ePlanReview 
Description
Plan Mod Scope:

Relocated sprinklers due to construction changes. Several areas are being entirely filled with noncombustible insulation in lieu of upright sprinklers.


Fire Work Scope:

The Fire Sprinkler Scope of work consists of three wet systems and one dry system in an existing school. Part of the basement system is existing. The building is three floors with an attic. There are numerous areas with above and below fire protection. There will be new 6" C900 underground installed to the building with and outside PIV. Several remote areas were calculated with 3000 sf. due to concealed combustible construction. The sprinklers for the most part are SSP and SSU. The attic utilizes smaller k-factor 4.2 sprinklers. There is a crawl space that is not sprinklered. Therefore there can be no storage in the crawl space.

(LOWELL ELEMENTARY) Remodel of an existing 41,741 sq. ft. school building, exterior site accessibility, additional parking and structural upgrade & connections as per engineering & per approved plans. Work includes select structural & interior finish demolition for the express purpose of removing asbestos, lead containing materials and finishes and to upgrade accessibility between floors within the building and from the exterior school site to the interior of the building and the public way to the school grounds; and to install a sprinkler / alarm systems throughout. Scope of work includes removal of doors, hardware & finishes; remodel administrative offices, workroom & lounge; install new doors and hardware; construct new elevator, ADA ramps, upgrade security, lighting, HVAC & plumbing; construct new interior walls, millwork and finishes; and all associated site work all as indicated in the reviewed plans. Permit BLD09-00888 is also attached to the same set of plans for a 692 sq. ft. garage/maintenance building. drs CUP09-00019 - Modification
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/13/20107/15/20107/15/2010APASS
DetailsForrest France
Final acceptance testing and inspection passed. See also project related FIR09-00449 for activity notes regarding this permit. Fire sprinkler permit finaled.
INSP-Final Inspection7/6/20107/8/20107/8/2010PNR
DetailsForrest France
Not ready per conversation with contractor.
INSP-Conference7/7/20107/7/20107/7/2010ADONE
DetailsForrest France
Regarding project completion, coordination with alarm work, and final inspection schedule.
INSP-Sprinkler Rough-in/Hydro6/7/20106/7/20106/7/2010PPART
DetailsForrest France
Hydrostatic testing for the first floor and basement level systems passed.
INSP-Sprinkler Rough-in/Hydro6/4/20106/7/20106/7/2010PPART
DetailsForrest France
Overhead rough-in at the basement and 1st floor levels approved for cover. Discussed items remaining for final.
INSP-Sprinkler Rough-in6/4/20106/7/20106/4/2010ACANC
DetailsForrest France
Basement Rough-In Kerry is the person to contact. Would tike to have this First thing in the morning. 8:00 am if possable. Inspection requested from web by: Brad Bettencourt Phone #: ###-#### Inspection cancelled from web by: Brad Bettencourt
INSP-Sprinkler Rough-in6/2/20106/4/20106/4/2010PCANC
DetailsTroy Cobbley
rOUGH-IN IN THE BASEMENT Inspection requested from web by: Brad Bettencourt Phone #: ###-#### Inspection cancelled from web by: Brad Bettencourt
INSP-Sprinkler Rough-in/Hydro6/2/20106/4/20106/4/2010PCANC
DetailsTroy Cobbley
200LB for the 1st floor system.Bard Inspection requested from web by: Brad Bettencourt Phone #: ###-#### Inspection cancelled from web by: Brad Bettencourt
INSP-Sprinkler Rough-in/Hydro6/2/20106/3/20106/2/2010PCANC
DetailsForrest France
200 LB for the 1st floor system. Brad Inspection requested from web by: Brad Bettencourt Phone #: ###-#### Inspection cancelled from web by: Brad Bettencourt
INSP-Sprinkler Rough-in5/17/20105/18/20105/18/2010APART
DetailsForrest France
Overhead install at the first floor approved for cover per annotations on stamped plan set marked with today's date with the exception of stair 127 not yet finished. Also noted head guards to be provided for upright heads at the gym.
INSP-Sprinkler Rough-in5/14/20105/17/20105/17/2010PCANC
DetailsTroy Cobbley
I spoke to todd and they were leaving the job site and I was not going to make it do to time constraints.. Todd said he would reschedule for tommorrow
INSP-Sprinkler Rough-in4/21/20104/22/20104/22/2010APART
DetailsForrest France
The remainder of overhead rough-in at the second floor drop ceilings is approved for cover including the main corridor and perimeter rooms. Verified fire resistive coatings at exposed wood above the ceiling grid, noted ball valve at one drop sprinkler head to be removed at the north end of the corridor.
INSP-Sprinkler Rough-in/Hydro3/29/20103/29/20103/29/2010PPART
DetailsForrest France
Todd Phone #: 941- 6014
INSP-Sprinkler Rough-in3/26/20103/26/20103/26/2010PPART
DetailsForrest France
See clouded areas marked on stamped plan set at the second floor level classrooms okayed for ceiling cover- Includes rough-in and final head locations. Classroom 202 at the south end is not approved for cover due to exposed combustible construction above the drop ceiling lacking protection. Seismic brace locations at the feed mains in the basement riser room are acceptable.
INSP-Sprinkler Rough-in3/2/20103/2/20103/2/2010PPART
DetailsForrest France
Overhead hydrostatic test for the new dry system at the attic passed inspection.
INSP-Sprinkler Rough-in/Hydro2/25/20102/26/20102/26/2010APART
DetailsForrest France
Concluded satisfactory 24 hr. air testing of the new dry system.
INSP-Sprinkler Rough-in2/24/20102/25/20102/25/2010APART
DetailsForrest France
Begin 24 hr. pneumatic testing of the new dry system at 11:00PM @41psig.
INSP-Sprinkler Rough-in2/16/20102/16/20102/17/2010PNR
DetailsForrest France
For overhead work at second floor stairways.
INSP-Sprinkler Rough-in2/11/20102/12/20102/12/2010APART
DetailsForrest France
Rough-in inspection for the attic dry system completed satisfactory, main tie-ins are not yet finished, discussed seismic bracing, overhead piping at second floor stairways, insulation fill at the main entry vestibule okayed.
INSP-Sprinkler Rough-in2/11/20102/11/20102/11/2010PCANC
DetailsTroy Cobbley
Cancelled due to time constraints and Micron plan review. I spoke to todd and the inspection will be rescheduled for tomorrow.
INSP-Sprinkler Rough-in2/1/20102/2/20102/2/2010PPART
DetailsForrest France
Tenting for cold cavity protection of wet system piping at the library room is satisfactory. Discussed inspection schedule for insulation fill at this area to meet NFPA 13 exceptions.
INSP-Sprinkler Rough-in1/21/20101/21/20101/21/2010PPART
DetailsForrest France
Overhead fire sprinkler installation at the library room 128 is acceptable. Cover okay pending satisfactory tenting for cold cavity protection. Also need to verify non-combustible insulation fill to meet the exception allowed for non-sprinklered concealed spaces per NFPA 13 as the uprights in this area per plans have been deleted.
INSP-Conference1/14/20101/14/20101/14/2010PDONE
DetailsForrest France
INSP-Sprinkler Rough-in1/7/20101/8/20101/8/2010APART
DetailsForrest France
Okay to cover remainder of sheetrock lid ceiling areas as marked on the approved plan set with today's date and initials.
INSP-Sprinkler Rough-in1/5/20101/7/20101/7/2010AFAIL
DetailsForrest France
Upright heads at three closets on the first floor are too far below the deck, two mech. shafts and one custodial closet are not yet piped. Remainder of sheetrock lids at the first and second floors are okay for cover- see annotations on plans with today's date for locations.
INSP-Conference12/8/200912/8/200912/9/2009PDONE
DetailsForrest France
Discussion regarding product listings for fire resistant coatings.
INSP-Conference11/4/200911/4/200911/4/2009ADONE
DetailsForrest France
Regarding sprinkler coverage at the main entry exterior canopy.
INSP-Conference10/5/200910/6/200910/6/2009PDONE
DetailsForrest France
On site conference regarding fire sprinkler coverage at the concealed space above the library room.