Permit Number | FIR09-00615 |
Status | Finaled |
Name |
SIMPLEX GRINNELL
|
Site Address |
11311 W CHINDEN BLVD
|
Project Name | Hewlett Packard Building 3 |
Customer Number | |
ePlanReview | |
Description |
This quick permit is to provide notification to an existing system to accomodate a tenant improvement. Devices are to comply with 2007 NFPA 72 mounting and spacing requirements. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V - 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. No written comments. Associated Building Permit: BLD09-01786 (Hewlett Packard Building 3) Permit for minor tenant improvements to an existing 76,450 sq. ft. space located on the first story of building 3 converting 4 storage rooms, each approximately 144 sq. ft. in area into small conference rooms with work to include the removal and replacement of interior finishes including door hardware, carpet and paint. All work to be done per the approved plans. This is a fully sprinkled building; any alterations to the sprinkler system will require a separate permit and shall comply with NFPA13 as regulated by The City of Boise Fire Department. CDM
|