INSP-Final Inspection | 2/12/2010 | 2/16/2010 | 2/16/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. The NAC wiring as shown on the plans is supposed to be 12ga but 14ga has been installed. The fire alarm vendor provided revised plans and calculations for the 14ga wire.
|
INSP-Final Inspection | 2/12/2010 | 2/12/2010 | 2/12/2010 | P | FAIL |
Troy Cobbley
|
|
|
The heat detectors in the garage need to be mounted at the ceiling as discussed, the a/v needs to be relocated within 15' of the end of the corridor, the NAC panel does not report trouble signals to the FACP. No devices have been tested or the a/v's activated and the interconnection between the NAC and the existing FACP has not been verified.
|
INSP-Sprinkler Rough-in/Hydro | 2/12/2010 | 2/16/2010 | 2/12/2010 | A | CANC |
Troy Cobbley
|
|
|
Tom is the onsite contact his no. is ###-####. Inspection requested from web by: Shawna Gates Phone #: ###-#### Inspection cancelled from web by: Shawna Gates
|
INSP-Final Inspection | 2/11/2010 | 2/12/2010 | 2/12/2010 | A | FAIL |
Troy Cobbley
|
|
|
No testing performed this morning since the electrician is still wiring up the panel and is having trouble finding the EOL on the door circuit.
|
INSP-Final Inspection | 2/11/2010 | 2/11/2010 | 2/11/2010 | P | CANC |
Troy Cobbley
|
|
|
Cancelled due to too many inspections, time constraints and Micron plan review. Inspection was originally scheduled for this morning but was changed to an afternoon. I spoke to the contractor about performing a morning inspection but he wanted an afternoon inspection. To be rescheduled for tomorrow.
|
INSP-Final Inspection | 2/9/2010 | 2/11/2010 | 2/11/2010 | A | CANC |
Troy Cobbley
|
|
|
I spoke to Tom and he stated that his office shoud be rescheduling for this afternoon.
|