ePlanReview | |
Description |
This quick permit is to provide a duct detector for a new unit and connect it to the existing fire alarm system. Per the contractor, the duct detector is programmed for alarm because the existing FACP is incapable of supervisory signals. Initiation of the duct detector shall shut down the unit and trigger all notification in the building. There are no written comments and no associated building permit.
|