Permit Information
Permit NumberFIR10-00040
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 500 E BAYBROOK CT
Project Namesupervalu
Customer Number 
ePlanReview 
Description
This quick permit is to provide a notification device in a new training/conference room and connect it to an existing notification circuit. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V - 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written comments. Associated building permit: BLD09-02291 *( supervalu )* FPP permit Wall const. of aprox. 43 ln ft to create two rooms and two phone rooms on the first floor grid lines f/g to 2/4.Removal of selected doors and frames as well as finshes as noted on the plans.Walls will be nonconbustable partitions. minor ele work to be permited.
In code editions prior to the 1997 UBC stair enclosures were allowed to exit into corridors as long as the corridor doors were protected as required for a stair enclosure. (one-hour rated, 450 degree temperature rated in this case.) In code editions prior to the 1982 UBC stair enclosures were allowed to be one-hour rated in buildings 4 stories or less in height regardless of the Type of Construction.
Adjacent suites on the first floor will be required to provide one-hour, 450 degree temperature rated doors, where required in corridor on future permits. This building is NOT fire sprinklered, alarm modifcations will requirea permit from the fire planreview dept. 301
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/23/20102/23/20102/24/2010PPASS
DetailsForrest France
Scope of fire alarm work per permit documents passed after hours site inspection.
INSP-Conference2/22/20102/22/20102/22/2010ADONE
DetailsForrest France
Regarding site inspection schedule for after hours testing.