Permit Number | FIR10-00081 |
Status | Finaled |
Name |
BOISE CITY
|
Site Address |
333 N SAILFISH PL
|
Project Name | CITY HALL WEST-A/V HEIGHT ADJ. |
Customer Number | |
ePlanReview | |
Description |
This quick permit is to move four wall mount notification devices up from 80" to 96" for clearance of white boards. Inspector to field verify the following: wall-mounted visual notification appliances shall be mounted such that the entire lens is not less than 80 inches and not greater than 96 inches above the finished floor or at the mounting height specified using the performance based alternative of (2007 NFPA 72 7.5.4.5) 2007 NFPA 72 7.5.4.1. No adjustments to the battery calculations or voltage drops necessary under this permit scope of work. No written review comments. No associated building permit.
|